สัมมนาและ Workshop ผลิตภัณฑ์โทมูระ ประจำเดือน Click >>
 

 

 
 
 

 

  Home Page > Products > Fire Alarm  
CP1004 Series สัญญาณแจ้งเตือนไฟไหม้

 

 

 


Product Features
The panels have the following key features:
· 4, 8, or 16 conventional input zones.
· 2 notification appliance circuits (NAC) with built-in synchronization for ANSI 3.41and Gentex.
· The panel comes with a 3 amp power supply.
· Dedicated alarm and trouble relays.
· 1 RS485 can be able to connect repeaters.
· Housed in a 335mm W x 264mm H x 88mm D metal enclosure.
· Enclosure supports two 12V, 7Ah backup batteries.

 

 

CK1000 Series สัญญาณแจ้งเตือนไฟไหม้

General
AC POWER : 90 to 270VAC, 50 Hz, 3.0 amps.
Wire size : minimum 14 AWG (2.0 mm2) with 600-volt insulation.
BATTERY : Sealed lead-acid batteries only.
Maximum charging circuit: 27.6VDC @ 0.8 amp for normal flat charge.
Maximum battery charger capacity : 18AH battery.

Specifications
AC POWER : 90 to 270VAC, 50 Hz, 3.0 amps.
Wire size : minimum 14 AWG (2.0 mm2) with 600-volt insulation.
BATTERY : Sealed lead-acid batteries only.
Maximum charging circuit : 27.6VDC @ 0.8 amp for normal flat charge.
Maximum battery charger capacity : 18AH battery.

Features
Four to Sixteen Style B (Class B) Initiating Device Circuits (IDCs). All zones accept two-wire smoke detectors and any normallyopen contact devices. Zones 1 - 16 configured as general alarm zones. All circuits are power-limited and supervised, meeting the latest ULC requirements using fuseless technology. Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs). NACs may be programmed: Silenceable, Non-Silenceable, Auto-Silence 1.25 amps of NAC power. 3.00 amps of total system power. Alarm, Trouble and Supervisor, relay output. 24 volt operation. Resettable four-wire smoke detector power @ 500 mA. Nonresettable power @ 500 mA. Integral battery charger capable of charging up to 18 AH batteries (batteries over 4 AH require use of the external battery backbox, or ULC listed equivalent). Disable/Enable control per IDC. Reverse polarity protection. The CK1000 Series Conventional Fire Alarm Control Panel is a 24 volt, four, eight, sixteen-zone, Class B, Conventional Fire Alarm Control Panel. Designed exclusively to meet the latest market requirements and future ULC codes, the highly costeffective CK1000 Series can be used in a variety of low- to midsized applications.

 

 

RP1016
FIRE ALARM Status:
When a fire alarm occurs, the corresponding zone red LED flashing and the
internal buzzer sounds. When “MUTE/TEST” button pushed, the alarm zone LED lights steady and the
buzzer silenced. When another new fire alarm occurs, the new zone red LED flash and the buzzer sound
again. In the fire alarm status, the fire alarm “FIRE OUT” relay active and output “NO, NC, C” relay
contacts

 

 

 

HC102
Conventional Manual Call Point
Operating Voltage Range : 9~28VDC Volts
Alarm Current : 45 mA @ 24 VDC
Operating Humidity Range :10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range : -10°C to 50°C (14°F to 122°F)
Dimensions : Length 140mm, Width 105mm, Depth 45mm
Weight : Net Weight 220g

 

 

 

SB106
Conventional Manual Call Point

  • Compatible with all the conventional fire alarm control panel
  • Can be reset by key
  • 470 Ohm resistance
  • Easy surface mounting Base included

 

 

SG109
Conventional Sound Strobe

  • Compatible with all the conventional fire alarm control panel
  • Long light life up to 40000 flahsed
  • High sound level up to 100dB
 

JL188-6"/8"/10"
Conventional Alarm Bell

  • Three module size of 6", 8", 10'
  • Compatible with all the conventional fire alarm control panel
  • High sound level up to 95dB
  • Easy installation bracket included
  • Steel material
 

WT105C
Conventional Heat Detector

  • Compatible with all the conventional fire alarm control panel
  • Unpolarized wire input
  • Wide range of operating voltages
  • High precision electronic thermistor
  • Built in microprocessor intelligent software
  • Two LEDs blink standby, provide 360° visibility
  • Insect-resistant screening
  • Twist-on mounting base with tamper lock
  • Remote Indicator LED can be connected.
 

YT102C
Conventional Smoke Detector

  • Compatible with all the conventional fire alarm control panel
  • Unpolarized wire input
  • Wide range of operating voltages
  • Unique optical sensing chamber
  • Built in microprocessor intelligent software
  • Two LEDs blink standby, provide 360° visibility
  • Insect-resistant screening
  • Twist-on mounting base with tamper lock
  • Drift compensation and smoothing algorithms
  • Remote Indicator LED can be connected.
 

FT103
Conventional Smoke & Heat Detector

  • Compatible with all the conventional fire alarm control panel
  • Unpolarized wire input
  • Wide range of operating voltages
  • Unique optical sensing chamber and High precision electronic thermistor
  • Built in microprocessor intelligent software
  • Two LEDs blink standby, provide 360° visibility
  • Insect-resistant screening
  • Twist-on mounting base with tamper lock
  • Drift compensation and smoothing algorithms
  • Remote Indicator LED can be connected.
 

YT142
4 - Wire Smoke Detector with Relay Output

  • Compatible with all the security alarm system
  • Alarm Relay Output (NO/NC can be adjustable)
  • Unpolarized wire input
  • Wide range of operating voltages (9V-28VDC)
  • Unique optical sensing chamber
  • Built in microprocessor intelligent software
  • Two LEDs blink standby, provide 360° visibility
  • Insect-resistant screening
  • Twist-on mounting base with tamper lock
  • Drift compensation and smoothing algorithms
 

 

 

 

 

 

 

 
 
 

Home | Products | Support & Services | Customer list | Online Demo | Download | Contacts

 
Copyright © 2009 P.S.P. Telecom (1989) CO.,LTD. All right reserved.